Grounding Interlocking of High-Speed Decentralized Equipment
- Share
- Issue Time
- Jun 18,2021
Summary
Grounding Interlocking of High-Speed Decentralized Equipment
•Project
Background:
When
operating high-speed dispersion equipment, workshop employees need to ground
the mobile tank to remove the static electricity that may be generated during
the operation. Sometimes the grounding fails due to employees forgetting to
ground or accidentally dropping the grounding clamp. It does not meet EHS
regulations and has risks. This project introduces electrostatic grounding
equipment to ensure good grounding of mobile tanks during high-speed
dispersion.
• Project Objectives:
The
interlocking of high-speed dispersion and grounding of the whole plant is
realized by introducing static grounding equipment. Only when the grounding is
good, the high-speed dispersion equipment can operate. If the grounding fails
during the production process, the electrostatic grounding equipment will also
interlock the motor to stop, avoiding the risk of poor equipment grounding.
• Brief introduction of Static Grounding
Monitoring System:
The
system is composed of the Controller (with visual alarm), the
Clamp
and Plug & Cable.
It provides a
visual green light indicating a confirmed grounding condition of the mobile tank
during the transfer of flammable and combustible materials. A red light
indicates the absence of dependable grounding. An interlock circuit inside the
control panel will prevent pumps and equipment from starting until a
satisfactory ground is established. The interlock circuit will also shut off
pumps and equipment if the ground is lost during the pumping operation.
Specifications:
Input Power: 85VAC to 250VAC 50Hz
Input Current: <60mA
Output Signal: On-Off signal
Monitoring Set Point: 10 ohms
Alarm: Visible alarm
Spiral Cable: Extendable to 5.3m (17.4ft.)
Output
Safety Parameters:
Um:250VAC,Uo:14.28VDC,Io:27.2mA,Po:97mW,Co:4.17μF,Lo:192mH
Indicator: Lamp (Green=satisfactory ground and red=no ground)
OperationTemperature: -20℃ to +55℃(-4℉ to +131℉)
EU-Type Examination Certification No.: Presafe 16 ATEX 8909X
QAN Certificate No.: Presafe 16 ATEX 7744Q
Standard:EN60079-0, EN60079-1, EN60079-11
Applicable Directive:2014/34/EU
Working Status:
Normal:
the indicator light is flashing green / the buzzer does not sound
Standby:
indicator light flashes red/buzzer alarm
Alarm:
indicator light flashes red/buzzer alarm
Features:
1.
Static clamp resistance inspection function: monitor whether the contact
between the electrostatic ground clamp and the mobile tank is good.
2.
Grounding body resistance inspection function: monitor whether this system is
in good contact with the factory grounding network.
3.
Different colors of LEDs show the standby status, alarm status and normal
grounding status of the equipment.
4.
The equipment meets the requirements of workshop grounding control, independent
system control, disperses system risks, and is convenient for operation and
daily maintenance.
5.
The alarm signal can be output to third-party equipment to facilitate the
realization of more extended functions. For example: large screen in workshop.